Apex Pressure Reducing Valve (Feed Valve) 110 kPa - FV12.2

Model: FV12.2

Apex Pressure Reducing Valve (Feed Valve) 110 kPa - FV12.2

Application:
Low and medium pressure hot water systems.  

Standards:

  • Complies with NZ Building Code G12 (2001)
  • Complies with NZS 4608:1992
  • Patent No. 504476  
  • Pressure compensated to give constant outlet pressure regardless of inlet pressure.
  • Silicon rubber diaphragm and washer - no heat loop required.
  • N.Z. forged, high quality, corrosion resistant DR brass body
  • Machined, assembled and 100% tested in N.Z.
  • One-piece forged brass fork with no water paths - no leaks!

Flow Chart:

Apex Pressure Reducing Valve (Feed Valve) 35kPa - FV3.7 Flow Chart

Installation:

  • Refer to Specifcations Tab for installtion guide
  • Can be installed in any orientation.
  • Do NOT install in the ground.
  • Do NOT apply heat near valve during installation.
  • Valve may require adjustment on site. To increase pressure turn adjusting screw clockwise (1 ½ turns = 1 metre head).
  • Valve must be either valve vented or open vented.
  • For increased flow rates or inlet pressure below 200 kPa [29psi], two valves in parallel may be required.
  • Where two valves are in parallel, each must have isolating valves on inlet.  

Apex Pressure Reducing Valve (Feed Valve) 35kPa - FV3.7

Inlet: 15mm, 1/2" BSP (male)
Outlet: 20mm 3/4" BSP (male)
Length: 138mm

  • Set Pressures:
    • FV3.7 - 35 kPa [5psi]  
    • FV7.6 - 65 kPa [9psi]
    • FV12.2 - 110 kPa [16psi]  
  • Adjustable pressure range:
    • FV3.7 & FV7.6 - 15 to 100 kPa [2 to 14psi]
    • FV12.2 - 50 to 150 kPa [7 to 22psi]  
  • Maximum Inlet Pressure and Temperature:
    • Maximum inlet pressure: 2000 kPa [290psi].
    • Plastic Cap: 40˚C  
    • Brass Cap: 80˚C - hot water valve
  • Minimum temperature: 1˚C

 